AMERICAN made OIL CHILLER, oil CHILLER knowledge DEPOT, AMERICAN made oil CHILLERS, cold as a ARTIC CHILL oil chillers, WATER CHILLER, better than a COOLING TOWER AMERICAN MADE Hydraulic oil CHILLER does oil & water temp have you in a TURMOIL, WASTER & OIL CHILLER AMERICAN MADE CHILLER, IS OIL CHILLER AND WATER CHILLER AMERICAN MADE AT water chiller knowledge DEPOT  QUALITY AMERICAN MADE CHILLER OIL COOLING AMERICAN WAY

 

 

HOME
About Us
Contact Us
Products
Download Specs
Chiller University
Drycleaners Page
Custom Pics
Sizing Formulas
Newsletter
Quote Form (pdf)
Hydraulic Cooling

   NASHVILLE

JEFFERSONVILLE

                                                           
 

                             CHILLER UNIVERSITY  

         

Orientation

General Studies

Chiller Designs

Chiller Service

Graduation

 
 

CHILLER SERVICE

 

      All service work performed on the refrigeration system should be done by licensed and trained refrigeration service technicians only.

 

      Troubleshooting the chiller:

 The chiller cycles on and off quite frequently.

  • Verify the load on the chiller. If the chiller is sized too large, it will cool the fluid too rapidly.
  • Check the differential setting in the digital controller "d1 and d2" are the differential settings for Set-points 1 and 2 respectively. If the application temperature is not really sensitive, perhaps setting the differential higher will alleviate the problem.
  • Check the flow rate of the fluid passing through the chiller. If the flow is too low the chiller may short cycle.
  • Verify that the unit is not cycling from any of the safety devices, such as flow switch or low pressure safety switch. If it is, determine the cause (dirty filter, low refrigerant...)

 

The chiller heat exchanger is freezing up.

  • Check the settings in the digital controller "ST1 and ST2". These are the set-points for the compressor(s) to turn on. If the settings are below 55 deg F, it is strongly recommended that a mixture of propylene glycol be used with the water to lower the freezing point of the water.
  • Check the water flow rate through the chiller. The absolute minimum water flow rate is 1.8 GPM per ton of heat exchanger. Example: A 5 ton chiller with 1 heat exchanger has a minimum water flow rate of 9 GPM. A 10 ton Heat chiller with 2 (five ton) heat exchangers has a minimum flow rate of 9 gpm divided across each heat exchanger or 18 gpm at the outlet of the chiller. The optimum GPM per heat exchanger per ton is 2.4 GPM. This will give the best performance rate and allow for a 10 deg delta or change in water temperature across the heat exchanger.
  • Check for flashing in the sight glass. Is the unit low on refrigerant?
  • Check for a clogged strainer or heat exchanger.
  • Check for proper pump operation and/or rotation.
  • Is there air in the water circuit?
  • Is the condenser clean?
  • Are there any restriction in the refrigerant lines?

The suction lines and/or the compressor is frosting up.

  • Sometimes, this can be normal, depending on the application. Oftentimes, it is a lack of refrigerant or lack of airflow across the condenser.
  • Check for any restrictions in the refrigerant lines.
  • Verify the controller settings are within the design parameters of the chiller. If this chiller was designed for 60 deg fluid and is being used to cool to 40 deg fluid, it is being used outside it's design parameters.
  • If equipped with a hot gas bypass, is the device operating properly? Is the hot gas solenoid opening.
  • Is there a de-superheating valve? Is the solenoid valve staying open?

 

Any questions for Professor C not addressed, request an answer here!